CABLING AND CONNECTIONS vacon • 63
24-hour support +358 (0)40 837 1150 • Email: [email protected]
6
6.2.2 Control terminal signals
OPT-A1
Terminal Signal Technical information
1 +10 Vref Reference voltage Maximum current 10 mA
2 AI1+ Analogue input,
voltage or current
Selection V or mA with jumper block X1 (see page 66):
Default: 0– +10V (Ri = 200 k)
(-10V…..+10V Joy-stick control, selected with a jumper)
0– 20mA (Ri = 250 )
3 GND/AI1– Analogue input common Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
4 AI2+ Analogue input,
voltage or current
Selection V or mA with jumper block X2 (see page 66):
Default: 0– 20mA (Ri = 250 )
0– +10V (Ri = 200 k)
(-10V…..+10V Joy-stick control, selected with a jumper)
5 GND/AI2– Analogue input common Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
6 24 Vout
(bidirectional)
24V auxiliary voltage
±15%, maximum current 250mA (all boards total);150mA
(from single board); Can also be used as external power
backup for the control unit (and fieldbus)
7 GND I/O ground Ground for reference and controls
8 DIN1 Digital input 1
9 DIN2 Digital input 2
10 DIN3 Digital input 3
R
i
= min. 5k
18…30V = "1"
11 CMA Digital input common A for
DIN1, DIN2 and DIN3.
Must be connected to GND or 24V of I/O terminal or
to external 24V or GND
Selection with jumper block X3
(see page 66):
12 24 Vout
(bidirectional)
24V auxiliary voltage Same as terminal #6
13 GND I/O ground Same as terminal #7
14 DIN4 Digital input 4
15 DIN5 Digital input 5
16 DIN6 Digital input 6
R
i
= min. 5k
18…30V = "1"
17 CMB Digital input common B for
DIN4, DIN5 and DIN6
Must be connected to GND or 24V of I/O terminal or to
external 24V or GND
Selection with jumper block X3
(see page 66):
18 AO1+ Analogue signal (+output)
19 AO1– Analogue output common
Output signal range:
Current 0(4)–20mA, R
L
max 500 or
Voltage 0—10V, R
L
>1k
Selection with jumper block X6
(see page 66):
20 DO1 Open collector output Maximum U
in
= 48VDC
Maximum current = 50 mA
Table 6-9. Control I/O terminal signals on basic I/O board OPT-A1