
72 • vacon CONTROL KEYPAD
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
7.3.1 Monitoring menu (M1)
You can enter the Monitoring menu from the Main menu by pushing the
Menu button right
when the
location indication M1 is visible on the first line of the display. How to browse through the monitored values
is presented in Figure 7-4.
The monitored signals carry the indication V#.# and they are listed in Table 7-1. The values are updated
once every 0.3 seconds.
This menu is meant only for signal checking. The values cannot be altered here. For changing values of
parameters see Chapter 7.3.2.
Figure 7-4. Monitoring menu
Code Signal name Unit Description
V1.1
Output frequency
Hz Frequency to the motor
V1.2
Frequency reference
Hz
V1.3
Motor speed
rpm Calculated motor speed
V1.4
Motor current
A Measured motor current
V1.5
Motor torque
% Calculated motor shaft torque
V1.6
Motor power
% Calculated motor shaft power
V1.7
Motor voltage
V Calculated motor voltage
V1.8
DC-link voltage
V Measured DC-link voltage
V1.9
Unit temperature
ºC Heat sink temperature
V1.10
Motor temperature
% Calculated motor temperature. See All in One
application manual.
V1.11
Voltage input
V AI1
V1.12
Current input
mA AI2
V1.13
DIN1, DIN2, DIN3
Digital input statuses
V1.14
DIN4, DIN5, DIN6
Digital input statuses
V1.15
DO1, RO1, RO2
Digital and relay output statuses
V1.16
Analogue output mA AO1
M1.17 Multimonitoring items
Displays three selectable monitoring values. See
chapter 7.3.6.5.
Table 7-1. Monitored signals
Note: The All in One applications embody more monitoring values.
V1
V14
READY
Local
13.95 Hz
READY
Local
13.95 Hz
READY
Lo ca l
RUN RUN
RUN
Monitor Output frequency
FreqReference
Comentarios a estos manuales